Selam PV1000

Selam PV Inverters 1000 solution for use in industrial solar power plants with a capacity of 1 MW or more.
Selam PV1000 inverters meet the requirements of international standards:

DSTU EN 62109-1: 2014 (VDE 0126-14-1)
Safety of power converters for photovoltaic power systems – Part 1: General requirements. (Safety of power converters for use in photovoltaic power systems. Part 1. General requirements).

DSTU EN 61000-6-2: 2015
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments. (Electromagnetic compatibility (EMC). Part 6-2. General standards. Immunity to the industrial environment).

DSTU EN 61000-6-4: 2014 / A1: 2011
Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission standard for industrial environments. (Electromagnetic Compatibility (EMC). Part 6-4. General Standards. Emission Standard for Industrial Environment).

DSTU EN 60529: 1991 / A2: 2014 (VDE0470-1)
Degrees of protection provided by enclosures (IP Code). (Degrees of protection provided by enclosures. IP code).

Selam PV1000 is a product completely manufactured in Ukraine, confirmed by U-1 certificate.кВ.

Selam PV 1000 inverters are designed to convert electrical energy received from solar photovoltaic panels into electrical energy of industrial frequency 50 Hz with voltage of 0.4 kV.
Selam PV 1000 Inverters equipped with monitoring and control functions, and have the ability to connect to the network of power plants using the Modbus protocol, as well as through optical fiber and Ethernet. This provides a cost-effective, safe and reliable mode of operation, as well as full control of the photovoltaic system. The communication structure allows the operator to perform continuous monitoring, failure analysis, reporting and performance statistics.

Invertor

Рic 1.

Tab.1 Specifications

Selam PV 1000
DC Input
Power (recommended) *1 640 – 1500 kW
Voltage range MMPT 547 – 1000 V
MMPT voltage range at 50 ° C 632 – 820 V
Max allowable current 1600 A
Number of DC Inputs up to 8 pairs
Overvoltage protection Class 2
AC Output
Power at cos ? = 1 (at 25 ° C) 1000 kVA
Power at cos ? = 1 (at 45 ° C) 910 kVA
Power at cos ? = 1 (at 50 ° C) 845 kVA
Power factor adjustable lag 0.9 – 1 – gap 0.9
Output voltage 405 V
Maximum current 1426 A
Network frequency 50 Hz
Current distortion <3%
Overvoltage protection Class 2
Main settings
Efficiency 3 Max. / Euro 98.9 % / 98.6 %
Working temperature -20 °C to +50 °C
Relative humidity 15 … 95% max, non-condensing
Degree of protection, DSTU EN 60529 IP 20
Installation height above sea level 1500 m
Dimensions (W x H x D) 2700 x 2130 x 600 mm
Weight 1850 kg
Equipment color RAL 7032
Network monitoring according to FNN (VDN, BDEW)
Alarm and control
Earth fault monitoring Yes
Overvoltage protection Yes
Contactor and switch position Yes
Fault Indicators (Optical) 3 status LEDs
Communications
Display Display 240 x 64 graphic LCD display and 4 display keys
Hardware RS 485, RS 232, CAN BUS, Ethernet Programmable inputs and outputs
Communication line ISDN, GSM, GPRS, DSL
Software / Protocol Modbus, Profibus DP, Web portal, CANopen CiA 437
  1. depending on local environmental conditions
  2. external transformer required
  3. Without Transformer (LV / MV)

The main nodes SELAM PV 1000

  1. Inverter control compartment
  2. Fan compartment
  3. Display and control panel
  4. emergency shutdown button
  5. DC / AC cable connection compartment
  6. Ventilation grates
  7. Cap
  • DC switch disconnector Q4
  • Inverter stack, display and control unit with communication components
  • AC filter
  • K7 contactor
  • Automatic switch Q26
  • Mains transformer (AC 6/10/35 kV)
module

Inverter complete substation IKTPB – 1000

Inverter complete substation IKTPB – 1000 The block-modular inverter substation 1 MVA is a complete solution for use in the complex (when photovoltaic panels are installed with a total capacity of more than 1 MW).
The design of the substations allows to implement solutions for the issuance of electricity in the network 6 (10) kV and 35 kV.

Table 2. Specifications – ICTBP – 1000 kVA.

ICTBP-1000
DC INPUT
Recommended power *1 640 – 1500 кВт
Voltage range 547 – 1000 V
DC voltage 1000 V
MPPT voltage range 550 – 820 V
Max. D.C 1600 A
Number of DC Inputs up to 8 pairs
AC Output
Power at cos ? = 1 (at 25 ° C) 1000 kVA
Power at cos ? = 1 (at 45 ° C) 910 kVA
Power factor adjustable lag 0.9 – 1 – gap 0.9
Connection on the side of CH *2 6 kV; 10 kV; 35 kV
Output current (max) at 25 ° C 1426 А
Network frequency 50 Hz
Current error <3%
Main settings
Efficiency 3 Max. / Euro 98.9 % / 98.6 %
Working temperature -30 °C to +40 °C °C
Relative humidity 15 – 95% non-condensing
Degree of protection, EN 60529 up to IP 54
Height above sea level 1500 m
Dimensions (W x H x D) 22,4 x2,5x 6,0*4 2,4 x2,5x 8,4*5
Weight 6 500 kg
Colour customized
Auxiliary equipment power consumption 4000 W
Electricity consumption at night 200 W
Air quality, DSTU EN60721-3-4 Class 4S2
Network monitoring FNN (VDN, BDEW)
Alarm and control
Earth fault monitoring Yes
Surge Protection Control Yes
Contactor and switch position Yes
System shutdown Yes
Fault Indicators (Optical) 3 status LEDs
Communications
Display Display 240 x 64 graphic LCD display and 4 display keys
Hardware RS 485, RS 232, CAN BUS, Ethernet, Programmable Inputs, Outputs
Communication line ISDN, GSM, GPRS, DSL
Software / Protocol Modbus, Profibus DP, Web portal, CANopen CiA 437
Overvoltage protection DC input, AC output, monitoring equipment, AC MV output
  1. depending on local environmental conditions
  2. face value according to customer requirements
  3. excluding loss in transformer
  4. container dimensions excluding transformer site
  5. IKTPB dimensions taking into account the dimensions of the transformer site (the transformer is installed outside)..
1000kv
  1. Block-modular building with insulated casing, lighting, ventilation, heating, air conditioning and fire alarm systems.
  2. SELAM PV 1000 inverter.
  3. RU – 0.4 kV
  4. RU – 10 kV.
  5. Power transformer 2000 kVA

Note: one SELAM PV 1000 inverter is included in the package of inverter substations with a rated power of 1 MVA, which increases the transformer with a rated power of 1000 kVA. Substations can be equipped with intelligent monitoring and control systems.

ikbp100kv2

Technical data of used step-up transformers for IKTPB – 2000.
TMG-1000

Options Dimension
1. Voltage class, kV
3. The number of phases 3
4. Frequency, Hz 50
5. Scheme and group of compounds
U/Un-5
6. Type of cooling Free cooling, oil cooling
7. Indoor or outdoor installation Outdoor
8. The presence of a protective casing and degree IP00 of protection ±2х2,5%
Availability of winding spurs and their parameters (voltage, power) 5,5±10%
Short-circuit voltage,% 10800+10%
Loss of short circuit, W 1500+15%

Inverter substation IKTBP – 2000

Inverter substation 2 MVA block-modular design
Tab3. Technical characteristics – IKTPB – 2000 kVA

IKTPB – 2000
DC Input
Recommended power *1 2 x (640 – 1500) kW
Voltage range 547 – 1000 V
DC voltage 1000 V
MPPT voltage range 550 – 820 V
Max. D.C 2 х 1600 A
Number of DC Inputs up to 16 pairs
Fuse size max. 315 A
Overvoltage protection Class 2
AC Output
Power at cos ? = 1 (at 25 ° C) 2 х 1000 kVA
Power at cos ? = 1 (at 45 ° C) 2 х 910 kVA
Power factor adjustable lag 0.9 – 1 – gap 0.9
Connection on the side of CH *2 6 kV; 10 kV; 35 kV
Output current (max) at 25 °C 1426 А
Network frequency 50 Hz
Current error <3%
Main settings
Efficiency *3 Max. / Euro 98.9 % / 98.6 %
Working temperature -30 °C до +40 °C
Relative humidity 15 – 95% non-condensing
Degree of protection, EN 60529 up to IP 54
Height above sea level/td> 1500 m
Dimensions (W x H x D) 2,4 x2,5x 6,0*4 2,4 x2,5x 8,4 5
Weight 8 500 kg
Colour customized
Electricity consumption CH <4000 W
Electricity consumption at night 2 x 200 W
Air quality, DSTU EN60721-3-4 Class 4S2
Network monitoring FNN (VDN, BDEW)
Alarm and control
Контроль замыкания на землю Да
Earth fault monitoring Yes
Surge Protection Control Yes
Contactor and switch position Yes
System shutdown Yes
Fault Indicators (Optical) 3 status LEDs
Communications
Display Display 240 x 64 LCD display
Hardware RS 485, RS 232, CAN BUS, Ethernet, Programmable Inputs, Outputs
Communication line ISDN, GSM, GPRS, DSL
Software / Protocol Modbus, Profibus DP, Web portal, CANopen CiA 437
Overvoltage protection DC input, AC output, monitoring equipment, AC MV output
  1. depending on local environmental conditions
  2. face value according to customer requirements
  3. excluding loss in transformer
  4. container dimensions excluding transformer site.
  5. IKTPB dimensions taking into account the dimensions of the transformer site (the transformer is installed outside).
2000kv
  1. Block-modular building with insulated casing, lighting, ventilation, heating, air conditioning and fire alarm systems.
  2. SELAM PV 1000 inverter.
  3. RU – 0.4 kV
  4. RU – 10 кВ.
  5. Power transformer 2000 kVA

Note: one SELAM PV 1000 inverter is included in the package of inverter substations with a rated power of 1 MVA, which increases the transformer with a rated power of 2000 kVA. Substations can be equipped with intelligent monitoring and control systems.

ikbp100kv2

Cabinets summarizing Selam ICPV

Cabinets summarizing Selam ICPV designed to collect power from a group of photovoltaic modules. Optionally can be equipped with equipment for monitoring photovoltaic modules. After upgrading with a microprocessor unit, they are the central point for measuring the performance and status of photovoltaic modules. Data is collected and transmitted to the central inverter (i.e., Selam PV 1000), this allows to optimize the control of the power plant as a whole at all levels including average voltage.

Selam ICPV
  • Combines 8, 12, 16 or 24 lines of PV generator
  • Detects malfunctions and reduces losses at an early stage.
  • Accurately accepts and measures:
    • – Оcurrents
    • -system voltage at intervals of 100 ms, reading averages for 1 min
    • -module temperature with an interval of 1 s, reading the average values for 1 min
  • CANopen DS-301 interface
  • Positive and negative cable entry through cable glands
  • Fusible inserts:
    • – positive pole, or
    • -positive and negative pole;
  • Controls the status of a DC arrester by interrogating the signal contact.
  • Built-in DC disconnect switch
    • – optionally with alarm contact
  • Self-ventilated
  • Reliable over its entire service life (over 20 years)

Monitoring and automatic control

Selam PV .LoG, Selam PV .SerV
Data loggers continuously collect all important data from the converters, from the combiner blocks, from the weather sensors and from the energy meter. They provide access to the current state of the entire system. Depending on the configuration, they are equipped with a built-in DSL router and / or data server as a mirror. An Ethernet switch with a fiber connection is included in all data loggers. These connections provide a ring network structure between IKTPB and a summing switchgear in photovoltaic power plants (the Summing switchgear is designed to collect electricity from all IKTPB and further transfer of electricity to the grid). All the products of SEMAG brand are part of the monitoring and management network, including:
  • Selam PV central inverters
  • Selam ICPV Combiner Boxes
  • Selam PV .LoG
  • Selam PV .SerV

The SCADA system can also monitor the following weather sensors:


  • measurement of radiation • measurement of precipitation and wind direction
  • supports interface for energy meters

Example of execution of Selam PV .LoG and Selam PV .SerV cabinets
An example of equipping a solar power plant with a total capacity of 4 MW

pr
  1. Selam ICPV
  2. Photovoltaics
  3. Photovoltaics
  4. Selam PV 1000